Online UPS Single Phase O/P-HXi3115L30

Key Features & Application
• True On Line Double Conversion Design
• Output inbuilt isolation transformer
• Wide Input Voltage Range
• User-friendly digital LCD display
• Cold Start Function
• High Crest Factor Circuit Design
• Advanced Battery Management
• Improved Input power factor
Model | HXi3115L30 |
INPUT | |
Voltage {VAC) | 285-470Vac @ 100% Load, Three Phase (4 wire) |
Frequency (Hz) | 50Hz±10%. |
Power Factor | >0.95 |
OUTPUT | |
Power (VA) | 15000 |
Power Factor | 0.9 |
Voltage(V) | 220/230/240 ± 1% |
Frequency(Hz) | 50 ± 0.1%. |
Waveform | Pure Sine Wave |
THDv | THD < 3% |
Overload | 125% of rated load last for 60second,150% of rated load last for 1 second |
Isolation Transformer | Inbuilt Isolation Transformer |
BATTERY | |
Battery type | VRLA or SMF |
Battery voltage | 240/360 vdc |
Charger current (Max) | 1~10 Amp Standard (Higher Rating optional) |
Recharge Time | < 10hours to 95% |
Other Features | |
Display | LCD display indicating (Input voltage ,Output voltage,Input frequency, Output frequency,load %,battery%) LED indications: Mains ,AC Mode,DC Mode,Low battery,Overload |
Alarm | Battery low voltage, abnormal power supply, UPS failure,Overload |
Protection | Protection for battery low voltage, overload, short circuit and over temprature. |
Noise (db) | <75 dB (1meter) |
Efficiency | Upto 90% |
Temperature & RH | 0 ~ 40°C ,0 ~ 95%, No condensation |
Dimension (WxDxH)mm | 350 x 650 x 795 |