uninterruptible power management

Single Phase UPS-MP1103L8

BP 650
Key Features & Application

  • High Frequency and double conversion on-line technology.
  • Fully digitalized microprocessor control.
  • Wide input voltage range
  • Highly Efficient upto 90%
  • High input power factor > 0.99
  • LCD display
  • Cold start
  • IGBT both Inverter & Rectifier stage.
  • Advanced battery management
  • Automatic battery charge in UPS OFF mode
  • Short circuit & overload protection.
  • EMI/RFI noise filter.
  • Smart RS232 communications with monitoring software
  • Optinoal SNMP Card slot.
  • High reliability digital control
  • Full protection function
MODEL MP1103L8
Capacity (VA/Watts) 3000 / 2400
INPUT  
Operating voltage range 110~300Vac
Operating frequency range 46~54Hz±0.5Hz or 56~64Hz±0.5Hz (auto sensing)
Power factor ≥0.99
OUTPUT  
Output voltage 220/230Vac±1%
Output frequency Sychronized with the utility on AC mode; 50Hz/60Hz±0.2% on Battery mode
Output  voltage THD <1.5% (linear load), <3% (Non Linear Load)
Crest Factor 3:1(max)
Efficiency ≥90%
BATTERY  
DC Voltage 96Vdc
Charge Current 6A
Typical recharge time 8 Hours(to 90% of full capacity)
SYSTEM FEATURES  
LCD indication 1. Input voltage/frequency, battery voltage, output voltage/frequency, load watt/VA and percent, inverter temperature
2. Operation mode such as “on line”, “on batt”, or “or bypass”
LED indication 1. Green LED for normal operation
2.Yellow LED for warning condition
3. Red LED for abnormal operation

Overload capability 1.  >110%, 30s turn to bypass mode;
2.   >150%, 300ms turn to bypass mode
Transfer time  Between AC Mode and Battery Mode : 0ms
Between AC Mode and Bypass Mode : 4ms (typical value 2.5ms)
Communication interface RS232 ; SNMP (optional)
ENVIRONMENTAL  
Operating temperature 0~40℃
Storage Temperature -25~55 ℃
Humidity range 0%~95% (non-condensing)
Altitude <1500m
Noise Level <45dB
PHYSICAL  
Net/Shipping Weight (kg)  20/22
Dimension W×D×H (mm) 478×483×88
Packing W×D×H (mm) 580×580×248
STANDARDS  
Safety IEC/EN62040-1; IEC/EN60950-1
EMC IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8