uninterruptible power management

Three Phase UPS-DSII3106L16

BP 650
Key Features & Application

  • High reliability of Design
  • High reliability during operation
  • Strong environmental adaptability
  • Optimization of high-performance battery
  • Comprehensive and reliable protection
  • Strong Redundancy/parallel ability
  • User-friendly network management
  • LCD accurately displays the status of operation and data for users.
  • Inbuilt Isolation Transformer
MODEL DSII3106L16
Capacity (VA/Watts) 6K/4.8K
Technology 3:1 phase, online double conversion
INPUT
Operating voltage range 380Vac±20% (“3Ph+N+PE”)
Operating frequency  range 50/60 Hz (±5%)
OUTPUT
Voltage range 220 Vac±1%
Frequency range 50/60Hz (±1%)
Power factor 0.8
Crest factor 3∶1 (max)
Max. efficiency 85%
THD <2% (Linear load)
Overload 110 ~125% 60s, 150%./200ms later, transfer to bypass, restore after unloading
BATTERY  
Battery voltage 192Vdc
SYSTEM FEATURES  
Transfer time 0 ms (Line mode→ battery mode)
LED display Utility status, inverter, bypass, battery status, UPS abnormal, overload
LCD display I/O voltage, frequency, battery voltage, load, internal temperature
Communication interface Dry contact /RS232 /Intelligent Monitoring Software 
ENVIRONMENTAL  
Operating temperature 0~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Noise level <58dB (1m from surface)
PHYSICAL  
Dimension W×D×H (mm) 305x585x864
Net Weight (kg) 112
STANDARDS  
Safety IEC/EN62040-1; IEC/EN60950-1
EMC IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8