uninterruptible power management

Three Phase UPS-GT33100L32

BP 650
Key Features & Application

  • DSP-controlled technology
  • Parallel redundancy upto 4 units
  • Wide input voltage and frequency windows
  • Easy-to-operate LCD display
  • High power density up to 500kVA for space saving
  • High power factor and low input distortion
  • Output power factor to 0.8 (0.9 optional)
  • ECO mode for energy saving
  • Common or separate battery
  • Programmable battery voltage from ±192Vdc to ±240Vdc
  • Intelligent charge modes with smart charge current adjustment
  • Megatec/Mod Bus protocol supported
  • Powerful charger built in
  • Versatile communication interfaces provided for different applications
  • Superior overload capability
  • Programmable control and monitoring software
  • Can be configured to single phase output
MODEL GT33100L32
Capacity (KVA) 100KVA
INPUT 
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208~478Vac
Operating frequency range 40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) 2%(100% nonlinear load)
Bypass voltage range Max.voltage: +15%(optional +5%,+10%,+25% ) Min. voltage: -45% (optional -20%,-30%) Frequency protection range: ±10%
Generator input Support
OUTPUT
Output voltage 380/400/415Vac,  (3Ph+N+PE)
Voltage regulation ±2%
Power factor 0.8/0.9(Customized)
Output frequency 1.Line Mode: ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) 2.Battery Mode: (50/60±0.2%)Hz
Crest factor 3:1
Harmonic distortion (THD) ≤2% with linear load ≤5% with non linear load
Efficiency >94.5%
BATTERY
Battery voltage Standard unit: ±216Vdc;   Long run unit Optional Voltage: ±192V\±204V\±216V\±228V\±240Vdc
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line Mode Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% shut down UPS immediately
Bat. Mode Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
EPO (optional) Shut down UPS immediately
Battery Advanced Battery Management
Nose Suppression Complies with EN62040-2
Audible & Visual Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD display Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage & Inner Temperature
Communication interface RS232,RS485,Parallel,Intelligent slot,Relay card(optional),SNMP card(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude < 1500m
Noise level <55dB
PHYSICAL
Dimension W×D×H (mm) 600×780×1600
Net weight (kg) 286
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8