Online UPS Three Phase O/P-GTM3360L32

BP 650
Key Features & Application

 

    • DSP-controlled modular redundancy technology
    • Parallel redundancy up to 4 units
    • Wide input voltage and frequency windows Easy- perate LCD display
    • High power density up to 480kVA for space saving
    • Unity power factor and low input distortion Output power factor at 0.9
    • ECO mode for energy saving Common or separate battery
    • Programmable battery voltage from 384Vdc(32No.} to 480Vdc (40No.)
    • Intelligent charge modes wi1h
    • smart charge wrrent adjustment SNMP/Mod Bus protocol supported
    • Versatile communication interfaces provided for different applications
    • Superior overload capability
    • Programmable control and monitoring software
    • Can be configured to Single phase output(O)
Model GTM3360L32
Capacity (KVA) 60KVA
INPUT  
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208~478Vac
Operating frequency range 40Hz-70Hz
Power factor  >0.99
Harmonic Distortion (THDi) 2% (100% nonlinear load)
Bypass voltage range

Max.voltage:+15%(optional +%%,+10%,+25%);MIn. voltage:-45%(optional -20%,-30%)

frequency protection range:+-10%

Generator input  Support
Output  
Output voltage 380/400/415Vac, (3Ph+N+PE)
Voltage regulation +-2%
Power factor 0.9
Output frequency

 1.Line Mode:+-1%/+-2%/+-4%/+-5%/+-10% of the rated frequency (optional)

2.Battery Mode:(50/60+-0.2%)Hz

Crest factor 3:1
Harmonic distortion (THDi)  <% with linera load ;<5% with non linera load
Efficiency >95%
BATTERY  
Battery voltage  Standard unit:+-216Vdc;Long run unit Optional Voltage:+-192V/+-204V+-216V/+-228V/+-240Vdc
SYSTEM FEATURES  
Transfer time Untility to battery :0ms; Utility to bypass:0ms

Overload

Line mode

Battery mode

 

Load <-110%:last 60min,<-125%:last 10min,<-150%:last 1min,>-150% Shut down UPS immediately

Load <-110%:last 10min,<-125%:last 1min,<-150%:last 55,>-150% Shut down UPS immediately

Short Circuit  Hold Whole System
Overhert Line Mode : Switch to Bypass ;Backup Mode : Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics  Upon Power on and Software Control
EPO (optional) Shut down UPS immediately

Battery

Noise Suppression

Audible & Visual

Status LED & LCD Display

Reading on the LCD display

Communication interface

ENVIRONMENTAL

Operating temperature

Storage temperature

Humidity range

Altitude

Noise level

PHYSICAL

Dimension W×D×H (mm)

Net weight (kg)

 

STANDARDS

Safety

 

 

EMC

Advance Battery Management

Complies with EN62040-2

Line Failure , Battery Low ,overload,system fault

Line Mode ,bypass mode,battery low,battery bad,overload & UPS fault

Input Voltage,input frequency,output voltage,output frequency,load percentage, Battery Voltage & inner Temperature

Rs232,Rs485,Parallel,Intelligent slot,Relay Card (optional),SNMP card (optional)

0℃~40℃

-25℃~55℃

0~95% non-condensing

<1500m

<55d

600×780×1200

158

 

 

IEC/EN62040-1; IEC/EN60950-1

 

 

IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;

IEC61000-4-5; IEC61000-4-6; IEC61000-4-8