uninterruptible power management

Three Phase UPS-MF3110L20

BP 650
Key Features & Application

 

  • N+X Parallel Redundancy
  • Online Double Conversion with DSP Control
  • Graphic LCD Display with Multifunction Parameter Settings
  • Unity Input Power Factor
  • High Output Power Factor at 0.8PF
  • Support Generator Input
  • Support Economic(ECO) Operation Mode
  • Settable Battery Voltage
  • Movable Bypass Module
  • Matching Battery Pack with Powerful Charger Built-in
  • Versatile Communication Interfaces Available
  • Communication Software
  • Optional: SNMP card/Relay card/ Parallel port module
  • Settable Charge Current
MODEL MF3110L20
Capacity (VA) 10000
INPUT
Nominal voltage 380/400/415; (3Ph+N+PE)Vac
Operating voltage range 208~478Vac
Operating frequency range 50Hz:45Hz~55Hz; 60Hz:54~66Hz (auto sensing)
Power factor ≥0.99
Bypass voltage range Max. voltage: +15% (optional +5%, +10%, +25% )
Min. voltage: -45% (optional -20%, -30%)
Frequency protection range: ±10%
ECO range Same as the bypass
Harmonic distortion (THDi) <5% (100% linear load)
Generator input Support
OUTPUT
Rated voltage 220/230/240Vac
Power factor 0.8 (Standard) / 0.9 (Optional)
Voltage regulation ±1%
Frequency(Line Mode) ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Bat. Mode 50/60(±0.2%)Hz
Crest factor 3:1
Harmonic distortion (THDi) ≤2% with linear load, ≤5% with non linear load
Waveform  Pure Sinewave
Efficiency >92%
BATTERY
Battery voltage 240Vdc
Backup time Depends on the capacity of external batteries Estimated remaining time displayed on the LCD
Typical recharge time 6-8 hours (to 90% of full capacity)
Charge current Max.current 6A
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload(Line Mode) Load≤110%: last 60min, ≤125%: last 10 min, ≤150%: last 1 min, ≥150% shut down UPS immediately
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
EPO Shut down UPS immediately
Battery Advanced Battery Management
Noise Suppression Complies with EN62040-2
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD display Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time
Communication interface USB,RS485, SNMP card, Parallel card, Relay card (optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude < 1500m
Noise level <55dB
PHYSICAL
Dimension W×DxH (mm) 270×570×720
Net Weight (kg) 39Kg
STANDARDS
Safety IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8