uninterruptible power management

Three Phase UPS-MP3120L16

BP 650
Key Features & Application

  • True double-conversion
  • DSP technology guarantees high performance
  • Output power factor 0.8
  • Wide input voltage range (120-276 VAC)
  • Active power factor
  • 50Hz/60Hz frequency converter mode
  • Eco mode operation for energy saving (ECO)
  • Emergency power off function (EPO)
  • Generator compatible
  • SNMP+USB+RS-232 multiple communications
  • Adjustable battery numbers
  • Optional N+X parallel redundancy
MODEL MP3120L16
PHASE 3 Phase IN / 1 Phase OUT
CAPACITY 20000 VA / 16000 W
INPUT
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range  305-478 VAC (3-phase) @ 100% load
190-520 VAC (3-phase) @ 50% load 
Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧ 0.99  @ 100% load
OUTPUT
Output Voltage 208/220/230/240VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦ 2 % THD (Linear Load)   ;   ≦ 5 % THD (Non-linear Load)
Transfer Time AC mode to Battery mode Zero
Inverter to Bypass Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 92%
Battery Mode 90%
BATTERY
Long-run Model Battery Type Depending on the capacity of external batteries
Numbers 16(16 – 20 adjustable)**
Charging Current (max.) 4 A
Charging Voltage 273 VDC ± 1%  (based on battery numbers at 20 pcs)
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Long-run Model Dimension, W X D X H (mm) 438 x 668 x 266(6U)
Net Weight (kgs) 45
ENVIRONMENT
Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 60dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows®  7, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser